HEATING COOLING MACHINE AVAILABLE FOR HIRE
ATEX, FLP MODELS AVAILABLE

Select your Model

Filter By Machine Type

-100℃~-30℃

Download PDF
ModelGX-A028N GX-A050N GX-A0A10N GY-A028N GY-A050N GY-A080N GY-A0A16N
Volume280L500L1000L280L500L 800L1600L
Inner dimension610*600* 760800*735* 8501000*1000* 1000800*600* 6001200*650* 6501350*800* 7502000*900* 900
Capacibility carrying150 kg220 kg300 kg150 kg220 kg300 kg650 kg
Cooling capacity0.7 kw -90oC1 kw -90oC2 kw -90oC0.7kw -90oC1kw -90oC 2kw -90oC 3kw -90oC
Temp. accuracy±2oC ±2oC ±2oC ±2oC ±2oC ±2oC ±2oC
Heating Power2 kW3 kW5 kW2 kW3 kW5 kW8 kW
Inside circulating air1650 m³/h 2100 m³/h 2750 m³/h 2100 m³/h 2750 m³/h 3500 m³/h 6000 m³/h
Dimension1150*1150 *18501350*1300 *18501550*1500 *21002200*1150 *11502700*1200 *12002900*1300 *12503700*1400 *1350
Power 380V 50HZ9 kW(max)13.5 kW(max)18 kW(max)12 kW(max)16.5 kW(max)20 kW(max)30 kW(max)
Weight470kg 580kg 750kg 495kg625kg810kg 940kg
  • Type
  • (Vertical) (Chest/Horizontal)
  • Capacibility carrying
  • Designed bearing capacity is two times of the standard one, (refrigeration system is designed according to the standard capacity when target artifact weight is greater than the standard capacity, the cooling rate will decrease)
  • Temp. range
  • -100oC~60oC
  • Heating power
  • Nickel-chromium alloy electric heating heater, the controller has double safety protection, with independent temperature limiter protection.
  • Cooling rate
  • (Ambient temperature of 25℃, no-load, from 60 ℃s to -95 ℃ about 1 hour).;cooling rate will be a little different for temperature changes.
  • Controller
  • ASET multifunctional controller
  • Operation panel
  • 7-inch color touch screen, display set temperature, measured temperature.
  • Temp. record
  • Temperature curve and fault record, U-disk data export, excel format.
  • Inside circulating air
  • When it is open, the internal circulation fan automatically turns off. The touch screen displays open state.
  • Compressor
  • Emerson Copeland, adopt cascade refrigeration technology
  • Intermediate heat exchanger
  • KAORI Plate heat exchanger
  • Dry filter
  • Emerson
  • Expansion valve
  • Electronic expansion valve
  • Evaporator
  • Copper-tube with aluminum-fin
  • Cooling Type
  • Air-cooled with water-cooled auxiliary functions (Ensure good cooling capacity when temp. above 30℃)
  • Means of insulation
  • Polyurethane foam insulation, thermal insulation layer 125 mm, with embedded FIR boards
  • Safety Protection
  • Self-diagnosis function; Phase sequence phase failure protection; leakage protector; cooling unit overload protection; high and low pressure switch, overload relay, thermal protection device, high temperature protection and temperature fault protection.
  • Case material
  • Outside is cold rolled steel painting, internal is SUS304 wire drawing board.
  • Refrigerant
  • R404A R23 R14
  • Optional
  • High temperature reaches 150oC and temperature accuracy is ±0.5℃;the input power will be changed (When select this model, the thickness of thermal insulation layer will be 150mm,thermal insulation material will be silicate and vacuum plate)
  • Optional
  • /
  • Optional
  • Temp. accuracy ±0.5oC
  • Optional
  • Cooling and heating program controlled, meet cold treatment process requirements(can set 5 programs, each program can edit 45 steps.)
  • Optional
  • Interior door, reduce cooling capacity lost when picking small workpieces (temperature below 60℃ optional)
  • Optional
  • Outside SUS304 wire drawing board case
  • Optional
  • Diameter 50mm cable hole
  • Optional
  • Electric heating vacuum glass observation window (with lighting) 200mm*300mm

MANUFACTURED BY

CONTACT US

We automate and customize based on your specific requirement. Connect with us.

Phone +91 9618595672
Email info@e3techsys.com
Head Office 30-15-189, 4th Floor, Fonta Plaza,
Dabagardens, Visakhapatnam - 530020
Western Region No.602, 6th Floor, World Trade Centre
Sayajiganj, Vadodara-390005
Southern Region 111/314 C (X/269), Gokulam , Ayani Road
Maradu, Kochi - 682304